Calculation Table

How Many Ventilators Do I Need?

COMMERCIAL/INDUSTRIAL

  1. Calculate the buildings M³ (Length x Width x Height)
  2. Determine the number of air changes required for the building type (Table 1)
  3. Next calculate the venting capacity M³/h (Table 2)

You will need to know:

  • Typical area wind speed (1m/s to 5m/s).
  • Temperature difference between indoors and outdoors (°C)
  • Roof height

4.   Insert the information into the formula to calculate the total number of ventilator

Table 1
Recommended * No. of air changes per hour
Building Type Air Changes P/Hr Building Type Air Changes P/Hr
Warehouses 3–5 Laundries 7–15
Factories/Workshops 3–8 Welding Workshops 12–21
Gyms/Sport halls 3–8 Animal Housing 10–50
Assembly Halls 6–12 Garages 6–12
Toilets 12–15 Cooking Factories 6–12

*Air change rate must conform to local health department’s code specific to building type.

Table 2
Temperature Difference between Indoors and Outdoors (°C)
3°C 5°C 10°C
Vent Size Wind Speed 6m10m15m20m 6m10m15m20m 6m10m15m20m
200mm Curved Vane1m/s180230320380300340410460350580700810
2m/s260370500590550680760830590750920930
3m/s470720770880730830930103080087010601075
4m/s7209001060115010001130125013201060125012801300
5m/s108011201230140011001230132013601180130013901430
300mm Curved Vane1m/s2703404204903604305005505107209401050
2m/s32051061076061074084093672087011101220
3m/s5809309601080870990110012001000109012801340
4m/s86012401290135012001300148015301310149015801680
5m/s131014801580164014501490163016801520167018101910
500mm Curved Vane1m/s91010901090141010001230145017501250157019902040
2m/s139015401570171014301570182020101630164022702530
3m/s164022462080221018402010225024202100225027102860
4m/s257026102610280024502650273029102620275032003300
5m/s311031203130322031203130337034403150338034103770
600mm Curved Vane1m/s121014501820205013901820221026001840234028503380
2m/s190020502300260020902310268030592360278032303690
3m/s264028803050314028302990325035103050338039204160
4m/s360036003720412036203770393041603830409044204740
5m/s432044504530488044504580471048704600486051305395
700mm Straight Vane1m/s213625422923328924912964346839882905345740454651
2m/s308734883907431334193863432747763786427847915289
3m/s469552585837639151535772640670155656633570327700
4m/s588764757123776463466980767983706841752582779022
5m/s7600813287019136796985279124958083568941956710046
900mm Straight Vane1m/s284833893897438533213952462453183873460953936202
2m/s441049835581616248845519618168245408611168457556
3m/s782587649728106528589961910677116929427105581172012833
4m/s93441027811306123241007311080121881328510859119441313914321
5m/s112591204712890135351180612633135171419312380132471417414883
formula

  M³ x air changes (table 1)

venting capacity (Table 2)        =      No. of ventilators Required*

*If this exceeds the amount of ventilators suitable to fit the roof with the recommended spacing of 6m (no less than 5m) then recalculate using a larger size ventilator.

RESIDENTIAL
House Size (m²) No. of Ventilators Required (200mm / 300mm)
Recommended Ventilation Guide
90–120 1–2
130–180 2–3
200–350 3–4
If you need any help to work out how many vents and what size and type are required for your building, please do not hesitate to contact us, or please provide your building dimensions of the area you are wanting to ventilate and we will provide a recommendation for you.

Frequently Asked Questions

To use the table, calculate your building’s total volume (length x width x height) and determine the required Air Changes per Hour (ACH) for your industry. You then match your total required airflow against our Exhaust Capacity Chart to see how many Skyaxis units are needed.

The number of vents is calculated by: (Building Volume × Required Air Changes) ÷ Vent Capacity. For a typical 90–120 m² home, 1–2 ventilators are generally required to maintain a healthy, dry environment.

Yes, the required air changes vary depending on the building’s use; for example, a standard warehouse may only need 2–5 air changes, while a hot factory may require 10 or more. Our calculator helps you adjust for these different requirements to ensure your ventilation system is fit for purpose.

The 300mm Skyaxis model is our standard recommendation for residential garages and sheds. It provides the ideal extraction capacity to effectively remove heat and moisture from these smaller spaces.

Yes, we offer free sizing calculations to ensure you get the correct number of vents for your specific building. Just send us your floor area, ceiling height, and building use, and our team will provide a tailored recommendation.

You should consider your roof height, local wind conditions, and internal heat loads. Factors such as the “stack effect” and higher coastal wind speeds can significantly increase the actual extraction rate beyond baseline calculations.

Follow our industry-specific “Air Changes per Hour” (ACH) guide and maintain a unit spacing of approximately 5–6 metres. This ensures consistent airflow across the entire building without the unnecessary cost of over-installing units.

REQUEST A WHOLESALE ACCOUNT

Architects, Engineers, Consultants, Building/Roofing Contractors, and HVAC Mechanical Services. Access specialised technical tools and preferred trade pricing.

Roofquip Logo
New Zealand's leading specialists in
passive industrial ventilation systems.
Engineered for the rugged Pacific
climate.
contact

© 2026 | Roofquip| All Rights Reserved | Designed by

Wholesaler Application

Wholesaler Form

Business Details

Get in touch with us

Contact Form